Vent Clearances and Framing

A. Pipe Clearances to Combustibles
WARNING
Fire Risk
Explosion Risk
Maintain vent clearance to combustibles as
specifi ed.
Do not pack air space with insulation or
other materials.
Failure to keep insulation or other materials
away from vent pipe may cause fi re.
3 in.
(76 mm)
Drywall
1 in. (25 mm)
2 x 4 or
2 x 6
header
Figure 6.1
Pipe Clearances
B. Wall Penetration Framing
Wherever a combustible wall is penetrated, the hole must
be framed with a wall shield fi restop. This shield maintains
minimum clearances and restricts cold air infi ltration.
If the wall being penetrated is of noncombustible materials
(material which will not ignite or burn, or has a UL fi re rating
of zero), a 9 in. (229 mm) diameter hole is acceptable.
Whenever a wall is penetrated the wall shield fi restop
is only required on one side and no heat shield is
necessary.
If your local inspector requires the wall shield fi restop on
both sides of the wall, then both wall shield fi restops must
have a heat shield attached to them.
26
Air space clearances
to bottom and sides
of horizontal pipe
must be at least
1 in. (25 mm)
No combustible
framing to be
located within
shaded area.
1/2 in. (13 mm)
minimum to
perpendicular
wall.
Heatilator • Caliber CNXT Series • 4047-132 Rev P • 11/07
Note: Heat shields MUST overlap by a minimum of 1-1/2 in.
(38 mm). The heat shield is designed to be used on a wall
4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness
is less than 4 in. (102 mm) the existing heat shields must be
field trimmed. If wall thickness is greater than 7-1/4 in. (184
mm) a DVP-HSM-B will be required.
Heat
Shield
Figure 6.2
Horizontal Venting Clearances to Combustible Materials
10 in.
12 in.
The center of the
framing hole is
1 in. (25mm) above
the center of the
horizontal vent pipe.
Framing should be
constructed of 2 X 4
lumber or heavier.
* Measured to center
Figure 6.3
Exterior Wall Hole
3 in. (76 mm)
top clearance
1 in. (25 mm)
Wall
clearance
Shield
bottom & sides
Firestop
WALL
42-1/4 in.
(1073 mm)*
27-1/4 in.
(692 mm)*
of pipe.
Heat
Shield