General Venting Information; Venting Support; Barometric Damper Location - A.O. Smith 400 - 2100 Installation & Operation Manual

Genesis water heater
Table of Contents

Advertisement

2
Venting
General information
You must supply adequate combustion and ventilation air to this unit. You must provide minimum clearances for the vent
terminal from adjacent buildings, windows that open, and building openings. Follow all requirements set forth in the latest edition
of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CAN/CGA Standard B149 Installation Code for Gas
Burning Appliances and Equipment or applicable local building codes. Vent installations for connection to gas vents or chimneys
must be in accordance with "Venting of Equipment" of the above-mentioned standards.
Examine the venting system at least once each year. Check all joints and vent pipe connections for tightness. Also
NOTICE
check for corrosion or deterioration. If you find any problems, correct them at once.

Venting support

Support horizontal portions of the venting system to prevent sagging. Provide an upward slope of at least 1/4 inch per foot
(21mm/m) on all horizontal runs from the unit to the vertical flue run or to the vent terminal on sidewall venting installations.
Do not use an existing chimney as a raceway if another appliance or fireplace is vented through the chimney. The weight of the
venting system must not rest on the unit. Provide adequate support of the venting system. Follow all local and applicable codes.
Secure and seal all vent connections. Follow the installation instructions from the vent material manufacturer.

Barometric damper location

Any venting system option that requires a barometric damper must adhere to the following directions for optimum performance.
The preferred location for the barometric damper is in a tee or collar installed in the vertical pipe rising from the unit's flue outlet.
The barometric damper MUST NOT be installed in a bull head tee installed on the unit's flue outlet. The tee or collar containing
the barometric damper should be approximately three feet vertically above the connection to the unit's flue outlet. This location
ensures that any positive velocity pressure from the unit's internal combustion fan is dissipated and the flue products are rising
due to buoyancy generated from the temperature of the flue products. Adjust the weights on the damper to ensure that draft is
maintained within the specified range.
MODEL
FLUE SIZE
400
500
650
750
--
*Minimum diameter for air inlet pipe. Installer may increase diameter one pipe size for ease of installation, if needed.
16
TABLE - 2A
FLUE AND AIR INLET PIPE SIZES
AIR INLET SIZE
6"
6"
6"
6"
8"
8"
8"
8"
--
--
Installation & Operation Manual
MODEL
FLUE SIZE
1000
10"
1250
12"
1450
12"
1800
14"
2100
14"
AIR INLET SIZE*
10"
12"
12"
12"
12"