Domestic water heaters

This section contains specific instructions for those appliances
used to supply domestic hot water. All warnings, cautions,
notes and instructions in the general installation and operation
sections apply to these instructions. Water heaters are designed
for installation with a storage tank.
A circulating pump MUST be installed in the piping assembly
to the storage tank and valves used to control water velocity
through the appliance. Proper water velocity is important for
correct operation of your water heater. The operation of the
circulating pump, proper sizing of the piping between the tank
and heater and the control of water velocity, as explained in
this section, are important for correct operation of your water
heater.
To ensure proper velocity through the heat
NOTICE
exchanger, it is necessary to regulate the
temperature rise across the heat exchanger
from inlet to outlet. This must be done
on initial installation and periodically
rechecked. With the correct temperature
rise across the heat exchanger when the
water heater is firing at 100% of rated
input, you may be assured of the proper
velocity in the tubes. This will yield long life
and economical operation from your water
heater.
Excessive lime/scale build-up in the heat
exchanger tubes is a result of restricted flow
and too little velocity in the tubes. Excessive
pitting or erosion in the tube is caused by
high water flow and too much velocity
through the tubes. Care should be taken
to measure temperature rise and maintain
velocity as follows:
Initial set-up of maximum water flow
On initial start-up of the Genesis the maximum water flow
through the heat exchanger must be manually set before normal
operation begins.
TABLE - 8A
MAXIMUM WATER FLOW
CAUTION: The maximum flow rate through a Genesis water
heater with a copper heat exchanger must be set to provide and not
exceed the following flow:
Model
400 - 750
1000 - 2100
52
If higher flow rates are required through the water heater, an
optional Cupro Nickel heat exchanger is available. Consult the
factory for specific application requirements.
The heat exchanger is capable of operating within the design
flow rates required for the water heater, storage tank(s), and
connecting piping. Erosion of the finned copper tubes may
occur if the flow rate exceeds the maximum allowable flow rate
through the water heater. The maximum flow rate through the
water heater must be adjusted. Maximum flow on Models 400
- 750 is 55 GPM and 90 GPM on Models 1000 - 2100. Flow rate
can be determined by measuring the temperature rise through
the water heater when it is firing at full rate input.
Model
1000
1250
1450
1800
2100
1. The pump must run continuously when the burner is
firing.
2. With the pump running and the burner in the water heater
in the off cycle, the inlet water temperature and outlet water
temperature readings on the Operator Interface should read
approximately the same temperatures. Water Temperature
Rise on the Operator Interface should read near zero.
3. Turn the water heater on and allow time for the temperature
to stabilize.
Operator Interface when the burner is firing at 100% of
rated input.
4. Compare the water temperature rise in the Operator
Interface with the required temperature rise.
adjustment be needed, proceed as follows.
Maximum Flow
55 GPM
90 GPM
Installation & Operation Manual
TABLE - 8B
TEMPERATURE RISE AT FULL RATE FIRE
55 AND 90 GPM FLOW
Temperature Rise
400
12°F (6.7°C)
500
15°F (8.3°C)
650
20°F (11.1°C)
750
23°F (12.8°C)
19°F (10.6°C)
24°F (13.3°C)
27°F (15°C)
34°F (18.9°C)
39°F (21.7°C)
Check the water temperature rise in the
Should