12. Electrical Connections/Wiring Cont.
The zone valve micro switch must be con-
nected to the terminal block situated next
to the control panel.
To fused spur
isolation switch
3
2
1
J
120 VAC Control
Terminal Block
Figure 12.10
When connecting the zone valve switch,
the jumper J in Fig. 12.10 must be re-
moved.
Route the electrical supply cord and the external control cord as illustrated in Fig. 12.12.
Lock the cords in place with the fl exible cord clamps.
Replace the control panel reversing the steps on page 23.
RIVA PLUS COMBI MANUAL
12.5
Zone Valve Micro Switch Connection:
L
N
Power supply
terminal block
External controls
terminal block
12.6
To the external
control device
Figure 12.12
3
Connect the micro switch of the zone
valve to terminals 1 and 3 as shown in fi g-
ure 12.11
Connect the zone valve switch to the room
thermostat as shown in fi gure 12.11

Finishing

To the fused spur
isolation switch
Zone
Room
Valve
Thermostat
V
T
N
L
1
120 VAC
Control Terminal
Block
Figure 12.11
29