Room Thermostat Connection; Relay Panel Control Connection - Biasi Riva Plus Combi Installation & Operation Instructions

Wall hung gas boiler for central heating supply
Table of Contents

Advertisement

12. Electrical Connections/Wiring Cont.
The room thermostat must be connected
to the terminal block situated next to the
control panel.
To fused spur
isolation switch
3
2
1
J
120 VAC Control
Terminal Block
Figure 12.6
Any external controls and connection lines
must be rated at 120 VAC but under no
circumstances should external live volt-
age be connected to the room thermostat
link on the boiler.
The relay control must be connected to
the terminal block situated next to the
control panel.
To fused spur
isolation switch
3
2
1
J
Figure 12.8
When connecting any type of relay con-
trol, the jumper J in Fig. 12.8 must be re-
moved.
28 RIVA PLUS COMBI MANUAL
12.3

Room Thermostat Connection:

L
N
Power supply
terminal block
External controls
terminal block
12.4
Relay Panel Connection:
L
N
Power supply
terminal block
External controls
terminal block
When connecting any type of external
control, the jumper J in Fig. 12.6 must be
removed.
The room thermostat must be connected
to the "Control Terminal Block" (Fig 12.7).
T
Room thermostat
(120V rating)
3
2
1
Figure 12.7
Connect the room thermostat between
terminals 1 and 3 as shown in Fig. 12.7.
Connect the dry contact switch of the re-
lay panel to the 120 VAC control terminal
block (Fig 12.9).
T
Generic Relay Control
3
2
1
Figure 12.9
Connect the dry contact switch to termi-
nals 1 and 3 shown in Fig. 12.9.
L
N
Power supply
terminal block
External controls
terminal block
(120V rating)
L
N
Power supply
terminal block
External controls
terminal block