Three Way Diverter Valve; Function; Checks; Removal Of The Electric Actuator - Biasi ActivA Plus Service Manual

Wall hung, fanflue, roomsealed, high efficiency gas boiler
Table of Contents

Advertisement

8

THREE WAY DIVERTER VALVE

8.1 Function

The diverter valve A (Figure 8.1) has the function of modifying the
hydraulic circuit of the boiler by means of an electric command
given by the electronic control p.c.b. in order to send the water
that exits the primary heat exchanger towards the c.h. system or
towards the d.h.w. heat exchanger.
Figure 8.1

8.2 Checks

Warning: check the electrical continuity.
Figure 8.2 indicates the relationship between the electric com-
mand coming from the electronic control p.c.b. and the position
of the actuator B (brass spindle) when the boiler operates in
d.h.w. mode.
Figure 8.3 indicates the relationship between the electric com-
mand coming from the electronic control p.c.b. and the position
of the actuator B (brass spindle) when the boiler operates in c.h.
mode.
,Q ERWK ¿JXUHV WKH UHODWLRQVKLS EHWZHHQ WKH SRVLWLRQ RI WKH DFWXD-
tor and the resistance of the motor windings (the motor must be
disconnected from the wiring) is also given.
THREE WAY DIVERTER VALVE
A
B
Spindle visible
Figure 8.2
D.h.w. mode
B
Spindle not visible
Figure 8.3
C.h. mode

8.3 Removal of the electric actuator

Warning: isolate the boiler from the mains electrici-
ty supply before removing any covering or compo-
nent.
1 Remove the front case panel.
2 Disconnect the connectors C (Figure 8.4).
3 5HPRYH WKH ¿[LQJ VSULQJ ' DQG UHPRYH WKH DFWXDWRU (
Reassemble the actuator carrying out the removal operations
in the reverse order.
When reassembling the actuator, refer to Figure 8.3 or to the
wiring diagram in section 3 for the correct wiring connection.
1
2
3
9,4 Kohm
Open circuit
bk
bu
bn
bk = black
bu = blue
bn = brown
1
2
3
Open circuit
9,4 Kohm
bk
bu
bn
bk = black
bu = blue
bn = brown
- 19 -