Option Board Parameters - Omron 3G3AX-MX2-PRT-E User Manual

Mx2/rx profibus option board
Hide thumbs Also See for 3G3AX-MX2-PRT-E:
Table of Contents

Advertisement

Table F-1 Option Board Parameters
PNU R/W Res
890
R
-
Commissioning mode status
W
-
Set commissioning mode
time
904
R
-
PPO Write format
911
R
-
PPO Read format
918
R
-
PROFIBUS node address
963
R
-
Baudrate on PROFIBUS
964
R
-
Option Board Identification
965
R
-
Profile code
967 R/W
-
STW
968
R
-
ZSW
915 R/W
-
Output PZD assignments
916 R/W
-
Input PZD assignments
Name
IND in
PNU
-
-
-
-
-
-
-
-
-
-
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10

Option Board Parameters

Description
0: Commissioning mode NOT active
1: Commissioning mode active
The number of seconds for commissioning mode to
remain active
1: PPO1, 2: PPO2, 3: PPO3, 4: PPO4, 5: PPO5
1: PPO1, 2: PPO2, 3: PPO3, 4: PPO4, 5: PPO5
The Option Board node address
0:
9.6kbps,
1: 19.2kbps,
3: 187.5kbps,
4:
500kbps,
7:
3Mbps,
8:
6Mbps,
10: 31.25kbps, 11: 45.45kbps
Array of words:
[1]: Manufacturer ID = 328,
[2]: Drive unit type = 1,
[3]: Firmware version = xxyy (Ver. xx.yy),
[4]: Firmware year = YYYY,
[5]: Firmware date = DDMM,
[6]: Number of drive Objects = 1
0302h
Current value of STW
Current value of ZSW
Modbus address mapped into output PZD1
0 (zero) means STW
Modbus address mapped into output PZD2
0 (zero) means HSW
Modbus address mapped into output PZD3
Modbus address mapped into output PZD4
Modbus address mapped into output PZD5
Modbus address mapped into output PZD6
Modbus address mapped into output PZD7
Modbus address mapped into output PZD8
Modbus address mapped into output PZD9
Modbus address mapped into output PZD10
Modbus address mapped into input PZD1
0 (zero) means ZSW
Modbus address mapped into input PZD2
0 (zero) means HIW
Modbus address mapped into input PZD3
Modbus address mapped into input PZD4
Modbus address mapped into input PZD5
Modbus address mapped into input PZD6
Modbus address mapped into input PZD7
Modbus address mapped into input PZD8
Modbus address mapped into input PZD9
Modbus address mapped into input PZD10
APPENDIX F
APPENDIX F
Inverter
Param
-
-
-
-
P180
2: 93.75kbps,
-
6:
1.5Mbps,
9:
12Mbps,
-
-
-
-
P160
P161
P162
P163
P164
P165
P166
P167
P168
P169
P170
P171
P172
P173
P174
P175
P176
P177
P178
P179
91