Configuring the Network

Step 7
!Caution
!Caution
3-2
Configuring the Network
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
26
Table 12 Configuration of input and output content (continued)
Param
P174
Input Register 5 con-
tents
P175
Input Register 6 con-
tents
P176
Input Register 7 con-
tents
P177
Input Register 8 con-
tents
P178
Input Register 9 con-
tents
P179
Input Register 10
contents
Restart the Inverter for the changes to take effect.
Note
When restarting the Inverter, wait for the Inverter power indicator to go out
before switching on again.
Action on Network Error (P045) is disabled when P181 is set to 1 (Keep the
output data upon a network failure) I.e. when a network error occurs, the
Inverter will continue normal operation with the last received output data.
Check the network related Inverter settings regarding PROFIBUS node
address and PROFIBUS map selection. Not doing so may result in unex-
pected operation.
Tip
Alternatively, P180 in Step 3 may be performed using the set-slave address
functionality of your PROFIBUS master or diagnostic tool.
Tip
Alternatively, Step 2 up to Step 6 may be performed using OMRON CX-Drive.
Tip
Alternatively, Step 7 may be performed by resetting the Option Board using
PNU972 (Refer to APPENDIX F Option Board Parameters).
Download the GSD file named OC_0C6A for the Option Board via the Omron
website http://industrial.omron.eu.
Download the GSD file named OC_0D2B for the Option Board via the Omron
website http://industrial.omron.eu.
Install / add this GSD file to the PROFIBUS master configuration program
used to configure your PROFIBUS master.
(It may be necessary to update the device catalogue before proceeding)
Add your PROFIBUS master to the network in the configuration program.
Add an Option Board to the network in the configuration program and open
the Option Board's settings.
Set the Option Board's node address (also referred to as station address) to
match P180 in the Inverter.
Choose a module that is supported by the selected device profile (Inverter
parameter P182).
Description
Modbus register mapped into PZD5 or flexible
input word 5
Modbus register mapped into PZD6 or flexible
input word 6
Modbus register mapped into PZD7 or flexible
input word 7
Modbus register mapped into PZD8 or flexible
input word 8
Modbus register mapped into PZD9 or flexible
input word 9
Modbus register mapped into PZD10 or flexible
input word 10
Section 3-2