Voltage Selector Switch
Disconnect or turn OFF all appliances or tools connected to the
generator before changing the voltage selector switch position.
The generator may be damaged if the switch position is changed with
loads connected and operating.
The power available to each receptacle depends on the position of the
voltage selector switch.
Switch
Position
120V ONLY
120V/240V
120V ONLY Position
When the voltage selector switch is in the 120V ONLY position, you do
not need to spread the load over the receptacles. You must, however,
make sure the load on any receptacle does not exceed its available
power shown in the table above and the total load does not exceed the
total current available.
Total Current Available:
30.0 A (EB4000X)
37.5 A (EB5000X)
45.8 A (EB6500X)
Receptacle
1
30A at 120V 30A at 120V 30A at 120V
2
20A at 120V 20A at 120V 20A at 120V
3
20A at 120V 20A at 120V 20A at 120V
4A
20A at 120V 30A at 120V 30A at 120V
4B
1
15.0A at 120V 18.8A at 120V 22.9A at 120V
2
15.0A at 120V 18.8A at 120V 20A at 120V
3
15.0A at 120V 18.8A at 120V 20A at 120V
4A-4B
15.0A at 240V 18.8A at 240V 22.9A at 240V
Available Power
EB4000X
None
OPERATION
EB5000X
None
EB6500X
None
35