If the inner fan is at middle wind and TA-TS≥-1'C, the fan motor turn to low fan and continue
running 1 minute at lease.
8.5.7
The ionizer and timer are available at cooling mode.
8.6

Auto mode

8.6.1
At auto mode, the range of work is 17'C~30'C (62'F ~88'F).
8.6.2
At auto mode, the inner fan speed is only judge by the TA and TS, people can't set it.
8.6.3
At auto mode, the air conditioner automatically selects one of following operation
modes: Cooling, Heating, Fan mode according to the temperature different between
TA and TS.
8.7

Fan mode

8.7.1
At the fan mode, the inner fan motor always on and compressor and outer fan motor off.
8.7.2
The display shows the ambient temperature at fan mode, the temperature can not be
adjusted.
8.7.3
The fan speed can by changed at fan mode; the auto fan mode function is same as the
fan speed control on auto mode at 24'c.
8.7.4
The ionizer and timer are available at fan mode.
8.7.5
8.8

Dry mode

8.8.1
At dry mode, the setting temperature can not be changed. The display shows the
ambient temperature.
8.8.2
The action of compressor at Dry mode.
8.8.3
At the dry mode, the fan speed can not be adjusted. The inner fan motor is at low fan
and the outer fan motor is at middle fan.
8.8.4
At the dry mode, the ionizer and timer are available.
8.8.5
If shut-down the unit, the compressor will shut-down at once, the inner and outer fan
will have 15s delay for shut down. If turn the unit to the fan or heating mode, the
compressor shut-down at once, the outer fan will have 15s delay only.