T7200D,E SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTATS
Setting System and Fan (select models)
The system default setting is Heat. The fan default is set
so the fan operates continuously in the Occupied and
Recovery modes and with the heating or cooling equip-
ment in the Unoccupied mode. Use the System and Fan
keys to change the settings.
The system settings are:
Heat: Thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: Thermostat controls the cooling.
Auto: Thermostat automatically changes between
heating and cooling operation depending on the
indoor temperature.
The fan settings are:
On: Fan operates continuously.
Auto: Equipment controls the fan in the Unoccupied
mode. The Intelligent Fan™ operation (Installer
Setup number 17) offers three choices for the fan
operation in Occupied mode:
— fan turns on only when there is a call for heating
or cooling,
— fan operates continuously in Occupied mode,
— fan is on continuously in Occupied and recovery
modes.

Setting Temperature

Refer to Table 1 for the default temperature setpoints. See
Owners Guide, form number 63-4356, for complete
instructions on changing the setpoints.
Table 1. Default Temperature Setpoints.
Control
Occupied
Heating
70°F (21°C)
Cooling
78°F (25.5°C)

INSTALLER SETUP

NOTE: For most applications, the thermostat factory-
settings do not need to be changed. Review the
factory-settings in Table 2 and if no changes are
necessary, go to the Installer System Test
section.
The Installer Setup is used by the installer to customize
the thermostat to specific systems. Installer Setup
numbers are listed in Table 2. The table includes all the
configuration options available.
A combination of key presses are required to use the
Installer Setup feature.
— To enter the Installer Setup mode, press and hold the
Heat/Cool Settings key while pressing both the
increase
and decrease
number is displayed. All display segments appear for
approximately three seconds before the number is
displayed. See Fig. 8 and 9.
62-0128—2
Unoccupied
55°F (13°C)
90°F (32°C)
keys until the first
— To advance to the next Installer Setup number, press
the Unoccupied Temp key.
— To return to a previous Installer Setup number, press
the Heat/Cool Settings key.
— To change a setting, use the increase
key.
— To exit the Installer Setup, press the Run Program
key. The Installer Setup is automatically exited if no
key presses are made for four minutes.
Set Program
Start Time
Em Ht
Em Ht
Aux Ht
Comm
Mon
TueWedThuFriSatSun
Un
Occupied 12 Override
System
Off
Cool
Em Heat
Fig. 8. LED display of all segments.
INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2
OF TABLE 2)
Fig. 9. Installer Setup number and setting display.
Installer Setup numbers are listed in Table 2.
CAUTION
Possible Equipment Damage.
Fan must be running when system is
operating.
Configure heat pump and electric heat systems in
Installer Setup 2 to prevent equipment damage
caused by the system running without the fan.
IMPORTANT
Only configurable numbers are shown on the
device. Example: If the thermostat does not have
a system key, Installer Setup Number 12 will not
be displayed. Review Table 2 factory settings
and mark any desired changes in the Actual
Setting column. When Installer Setup is com-
plete, review the settings to confirm that they
match the system.
4
or decrease
Temporary Setting Enrg
Set Day/Time
Set Day/Time
AM
PM
Heat
Cool
Recovery
Only
In
Auto
Lo
Med
Hi
Fan
Auto
Wait
FACTORY SETTING
OR OTHER CHOICE
DISPLAY (COLUMN 3
OR 5 OF TABLE 2)
Sav
Room
%Humid
Remote
Duct
On
Auto