Procedures for loading event configuration data

Procedures for loading all parameters

Handling Precautions
This procedure loads event configuration data on the memory card onto the
DCP552.
Data delete check
D e l e t e O l d D a t a
L O A D ?
LOAD key
Load completed
E V E N T D a t a
L O A D G o o d
This procedure loads all parameters on the memory card onto the DCP552.
Data delete check
D e l e t e O l d D a t a
L O A D ?
LOAD key
Load completed
A l l P a r a m e t e r s
L O A D G o o d
The DCP552 Mark II and the old model, DCP552, differ in how some setup
data items are processed and the range of variable parameter PA15. Thus
the following changes have to be made when setup data, variable
parameters or all parameters saved on a DCP552 are loaded onto a
DCP552 Mark II.
• Setup data
• Variable parameters : PA15, PA25
Setup data and all parameters stored on a DCP552 Mark II cannot be
loaded onto a DCP552. (A loading attempt generates card error 16.)
Chapter 9. MEMORY CARD OPERATIONS
DISP key
Normal display mode
(Load operation is not performed.)
DISP key
Normal display mode
DISP key
Normal display mode
(Load operation is not performed.)
DISP key
Normal display mode
: C21, C22, C45 to C50, C80, C90 to C97
9-9