Normal operation – Stage 4
Once the ice level control opens, the B-E LED goes out. After a 10 second delay the compressor LED (C),
compressor and fan motor go off. (Should the ice level control not remain open for 10 seconds, the ice machine
will continue to run.) The gearmotor continues to run and the DR LED remains on for 60 seconds. The purpose
of this function is to drive the remaining ice out of the evaporator and to boil off any refrigerant remaining in the
evaporator. The bin timer LED (BT) comes on, starting the twenty minute off cycle time delay.
GREEN/YELLOW
BROWN
BLUE
BLACK
ORANGE
ORANGE
BLACK
Normal operation – Stage 5
The drive motor now shuts down and the DR LED is off. The B-T LED remains on for 20 minutes. The ice machine
will not start while the B-T LED is on. To restart the ice machine for troubleshooting purposes, depress the reset
button to clear the control board.