Unspecified Voltage (Between Indoor And Outdoor Units) - Daikin CTXS09GVJU Service Manual

Super multi nx g-series
Hide thumbs Also See for CTXS09GVJU:
Table of Contents

Advertisement

Troubleshooting
5.8

Unspecified Voltage (between Indoor and Outdoor Units)

UA
Remote
Controller
Display
Method of
The supply power is detected for its requirements (different from pair type and multi type) by the
Malfunction
indoor / outdoor transmission signal.
Detection
Malfunction
The pair type and multi type are interconnected.
Decision
Conditions
Supposed
Causes
Troubleshooting
124
Wrong models interconnected
Wrong indoor unit PCB mounted
Indoor unit PCB defective
Wrong outdoor unit PCB mounted or defective
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the indoor
and outdoor unit
model numbers.
Indoor unit and
outdoor unit matched?
YES
Check the code numbers
(2P01234, for example) of the
indoor and outdoor unit PCB with
the Parts List.
Matched compatibly?
YES
NO
NO
SiUS12-814
Match the compatible models.
Change for the specified PCB
(1) or (2).
Replace the indoor unit PCB
(or the outdoor unit PCB).
(R7181)