The permissible rated operational current of the 3RM1 motor starter is reduced as shown in
the diagram depending on the installation altitude:
Note
Maximum installation altitude of 3RM11/3RM13 Failsafe motor starters: 2000 m
Installation altitudes of more than 2000 m are not admissible for 3RM11/3RM13 Failsafe
motor starters.
From an installation altitude in excess of 2000 m, in the case of Standard 3RM10/3RM12
motor starters the maximum permissible operational voltage must be reduced due to the
limited insulation strength. You can obtain details on request from SIEMENS Technical
Assistance (http://www.siemens.com/industrial-controls/technical-assistance).
SIRIUS 3RM1 motor starter
Manual, 11/2013, A5E0345285095020A/RS-AB/002
4.1 Rated operational current and derating