Daikin VRV III-S RXYMQ36 48PVJU Service Manual page 86

R-410a heat pump 60hz
Table of Contents

Advertisement

SiUS34-907
b. "Setting mode 2"
Push and hold the MODE (BS1)
button for 5 seconds and set to
"Setting mode 2".
<Selection of setting items>
Push the SET (BS2) button and set
the LED display to a setting item
shown in the table on the right.
Push the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
<Selection of setting conditions>
Push the SET (BS2) button and set
to the setting condition you want.
Push the RETURN (BS3) button and
decide the condition.
Push the RETURN (BS3) button and
set to the initial status of "Setting
mode 2".
∗ If you become unsure of how to
proceed, push the MODE (BS1)
button and return to setting mode 1.
Test Operation
No.
Setting item
Cool/heat unified
1
address
Low noise/demand
2
address
Test operation
3
settings
Indoor unit forced
5
fan H
Indoor unit forced
6
operation
8
Te setting
9
Tc setting
Defrost changeover
10
setting
External low noise
12
setting / Demand
setting
13
AIRNET address
Setting of hot water
16
heater
Additional refrigerant
20
charge operation
setting
Refrigerant recovery
21
/ vacuuming mode
setting
Night-time low noise
22
setting
Setting of external
25
low noise level
Night-time low noise
26
operation start
setting
Night-time low noise
27
operation end
setting
Power transistor
check mode
∗Check after
28
disconnection of
compressor wires
Capacity priority
29
setting
30
Demand setting 1
Normal demand
32
setting
The numbers in the "No." column represent the number of times to press the SET
(BS2) button.
Description
Sets address for cool/heat unified operation.
Address for low noise/demand operation
Used to conduct test operation without making changes to
the PCB and replacing the refrigerant, after the completion
of maintenance.
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
Allows forced operation of indoor unit.
Target evaporation temperature for cooling
Target condensation temperature for heating
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
Reception of external low noise or demand signal
Set address for AIRNET.
Make this setting to conduct heating operation with hot
water heater.
Carries out additional refrigerant charge operation.
Sets to refrigerant recovery or vacuuming mode.
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on "Starting set" and "Ending
set".
Sets low noise level when the low noise signal is input from
outside.
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PCB.
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and nighttime low noise operation.
Changes target value of power consumption when demand
control 1 is input.
Normally enables demand control 1 without external input.
(Effective to prevent a problem when a circuit breaker of
small capacity is shut down due to large load.)
Field Setting