Daikin VRV III-S RXYMQ36 48PVJU Service Manual page 25

R-410a heat pump 60hz
Table of Contents

Advertisement

Specifications
Wall Mounted Type
Model
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output
Airflow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB (27°CDB), 67°FWB (19.4°CWB)
Outdoor temperature: 95°FDB (35°CDB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°CDB).
Outdoor temperature: 47°FDB (8.3°CDB), 43°FWB (6°FWB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
16
FXAQ07MVJU
Btu/h
7,500
Btu/h
8,500
White (3.0Y8.5/0.5)
in. (mm)
11–3/8 × 31–1/4 × 9 (289 x 794 x 229)
2×14×17
ft² (m²)
1.73 (0.5)
QCL9661M
Cross Flow Fan
kw
0.04
cfm
260/160
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ1/4 (6.4) (Flare Connection)
in. (mm)
φ1/2 (12.7) (Flare Connection)
in. (mm)
VP13
in. (mm)
(External Dia. 11/16 (17.5)
Internal Dia. 1/2 (12.7))
Lbs (kg)
25 (11)
dBA
36
Fuse
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
FXAQ09MVJU
9,500
10,500
White (3.0Y8.5/0.5)
11–3/8 × 31–1/4 × 9 (289 x 794 x 229)
2×14×17
1.73 (0.5)
QCL9661M
Cross Flow Fan
0.04
280/175
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ1/4 (6.4) (Flare Connection)
φ1/2 (12.7) (Flare Connection)
VP13
(External Dia. 11/16 (17.5)
Internal Dia. 1/2 (12.7))
25 (11)
37
Fuse
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
C:3D046038A
SiUS34-907
FXAQ12MVJU
12,000
13,500
White (3.0Y8.5/0.5)
11–3/8×31–1/4×9 (289 x 794 x 229)
2×14×17
1.73 (0.5)
QCL9661M
Cross Flow Fan
0.04
300/180
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Foamed Polystyrene /
Foamed Polyethylene
Resin Net (Washable)
φ1/4 (6.4) (Flare Connection)
φ1/2 (12.7) (Flare Connection)
VP13
(External Dia. 11/16 (17.5)
Internal Dia. 1/2 (12.7))
25 (11)
38
Fuse
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Installation Panel, Paper
Pattern for Installation, Insulation
Tube, Clamps, Screws.
Specifications

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R-410aVrv iii-s rxymq36-48pvju

Table of Contents