SiUS34-907
U2
3.37 "
" Power Supply Insufficient or Instantaneous Failure
U2
Remote
Controller
Display
Applicable
RXYMQ36 · 48PVJU
Models
Method of
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Detection
Malfunction
When the voltage aforementioned is not less than 780V or not more than 320V, or when the
Decision
current-limiting voltage does not reach 200V or more or exceeds 740V
Conditions
Power supply insufficient
Supposed
Instantaneous power failure
Causes
Open phase
Defect of outdoor control PCB
Main circuit wiring defect
Faulty compressor
Faulty fan motor
Faulty connection of signal cable
Troubleshooting
Troubleshooting by Indication on the Remote Controller
175