Installation And Draft Considerations - Heat & Glo BIR50 Installation And Operating Instructions Manual

Woodburning fireplace
Table of Contents

Advertisement

North Star
EPA Certified Fireplace
The North Star Fireplace requires a minimum flue draft of -0.10 inches of water column on High, and -0.04 inches
of water column on Low, as measured with a draft meter. Most dealers have draft meters available to measure your
flue draft if you suspect a problem.
If the fire is difficult to start, and smoke spills out of the door, or you find it hard to establish and maintain a moderately high
burn rate, then the flue draft is too low and corrective measures must be taken.
The outside air kit is installed on the right hand side of the fireplace.
1.
Cut a 6" hole in outside wall to accommodate outside air
piping.
2.
Use 6" metal flex or rigid piping (not supplied) to directly
connect outside air to fireplace intake. Secure with hose
clamp.
3.
Use the supplied termination cap with a rodent screen.
4.
Seal between the wall and the pipe with silicone to prevent
moisture penetration.
NOTE: A control knob allows you control of the outside air inlet.
Use of outside air for combustion is required to conserve heated
air within the structure and to provide make up air to keep the
fireplace venting properly.
IMPORTANT!!
OUTSIDE AIR MUST BE IN OPEN POSITION TO OPERATE FIREPLACE PROPERLY
480-1081

INSTALLATION AND DRAFT CONSIDERATIONS

Location
Not
Marginal
Recommended
Recommended
Location
Location
Cathedral Ceiling Construction
OUTSIDE AIR KIT INSTALLATION
2nd Floor
Balcony
1st Floor
4
Recommended
Location
Location NOT
Recommended
Multi-level Roofs
4-03