AC Power (Mains) Connections

ANG_EN Power
Supply
WARNING
Instructions
Installation Note
18
Installation
The ANG_EN Power Supply can accept 90-264 VAC, 47-63 Hz inputs
without the need for setting switches or jumpers.
Installation personnel shall adhere to all AC Power (Mains) Specification
requirements; see Chapter 1. Specifications; page 3. Failure to do so,
and operating the equipment in a manner not specified, can impair the
safety protection provided by the equipment.
Step
1.
Shut off the primary AC Power Supply line to this location.
2.
Open the front panel of the ANG_EN by loosening the four
captive screws located on each corner; use 4mm Allen
wrench.
3.
Install a 15-Ampere circuit breaker, disconnect switch or a
receptacle in the power supply line or a switched receptacle
near the ANG_EN unit to make sure the unit can be com-
pletely separated from the power source. Label the breaker
or receptacle box to make sure that the circuit is clearly
identifiable.
4.
Remove the wiring access plate; see Figure 2-5. Punch
holes as required for either conduit or cable gland connec-
tors. Install connectors and replace the plate.
5.
Route input power, in accordance with pertinent electrical
codes and regulations, to ANG_EN.
To make the connections easier we have provided J1 as a removable
connector. Simply grasp the top portion of the connector and pull it
straight out from the base connector.