CE Installations

Description
CE Installation Kit
Instructions
Installation with Steel
Conduit
Installation without Steel
Conduit
2000590-001
This section should be used for installation sites that must conform to CE
(Conformite Europeene) Certification. Typically, this does not apply to
installations outside the EC unless the equipment was purchased with
the explicit requirements and expectations that it shall conform to EC
Electromagnetic and Radio Frequency Interference (EMI/RFI) rejection
specifications.
Available from Siemens Applied Automation CE Installation Kit P/N
2020264-001. This kit has all the parts for all the installations referenced
in this section.
The following information pertains to CE Installation of General Purpose,
Zone 1 and Division 2 Equipment. For Zone 1 Installations all cabling is
terminated in the ANG_EN Zone 1 Enclosure.
The preferred method is to route the field wiring in steel conduit. If steel
conduit is used unshielded power and signal wires can be used. The
power and signal wires (Ethernet and Data Hiway) must be routed in
separate conduit.
Using flexible conduit and/or armored cable is equivalent to using "steel
conduit". Flexible conduit or armored cable must have its flexible conduit
and/or armoring conductivity 360-degree terminated at its entry to the
ANG_EN enclosure (or bulkhead).
If conduit is not used, the following installation practices must be used to
ensure that the CE certification remains valid:
1. A shielded power cord or cable must be used for the input power
wiring. The shield must be terminated at the ANG_EN in a 360-
degree termination at the enclosure (bulkhead); use Siemens Ap-
plied Automation P/N 2015729-001 contained in the CE Installation
Kit or an equivalent part. For Zone 1 Installation use Siemens Ap-
plied Automation P/N 1311001-014 Installation Kit.
2. The Data Hiway cables shields must be terminated in a 360-degree
termination at the enclosure or bulkhead; use Siemens Applied
Automation P/N 2015729-001 contained CE Installation Kit or an
equivalent part. For Zone 1 Installation use Siemens Applied Auto-
mation P/N 13111001-014 Installation Kit.
Installation
15