B. Clearance to Combustibles
Maximum Mantel Depth: 12 inches (305mm)
B
A
F
Hearth Extension
INSTALLATION: Masonry, Heat Circulating and *Zero Clearance
With 8" Mantel Deflector, Part No. 831-1530
Maximum Mantel Depth: 12 inches (305mm)
*Zero Clearance in USA Only.
C. Optional Mantel Deflector
Optional mantel deflectors may be purchased from your
dealer to reduce clearances to a mantel. An 8 inch (203mm)
deflector allows a reduction down to  inches (686mm).
WARNING
Fire Risk.
• Comply with all minimum clearances to
combustibles as specified.
• Failure to comply may cause fire.
September 1, 2008
5100-I ACT WOOD INSERT
Mantel
Fascia or Trim
C
D
Insert
E
A
B
12" (305)
40" (1016)
12" (305)
27" (686)
In Canada a full length 6 inch (15mm) ULC S65 flue
liner required as per ULC S68.
NOTE: When installing into a masonry fireplace, the fire-
place must be built to UBC Chapter  standards. Do not
remove brick or mortar from masonry fireplace to accom-
modate insert. The permanent metal warning plate pro-
vided must be attached to the back of the fireplace stating
the fireplace may have been altered to accommodate the
insert and must be returned to original condition for use as
a conventional fireplace.
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having jurisdiction.
C
D
35" (889)
7" (178)
16" (406)
7" (178)
Figure 9.1
438-0380D
E
F
16" (406)
8" (200)
18" (450) Canada
16" (406)
8" (200)
18" (450) Canada