Fan Module—Displays the Server Intake and Server Exhaust Temperature as well as the RPM of each
fan
Water Inlet Temperature—Displays the temperature of the water coming into the MCS-200 unit to be
used to cool the servers
Water Outlet Temperature—Displays the temperature of the water after removing the server heat
Water Flow—Displays the value of the water flow in liters/gallons per minute

Management module components

The management module is located on the lower front of the MCS-200 unit, behind the front door.
Item Reference
C key
1
Power/alarm LED
2
Mini USB
3
connection
Description
Used to confirm warnings, critical alarms, and
configuration setting changes, as well as to turn off the
audible alarm. To confirm these situations, press and
hold the C key for five seconds, or click the Clear Alarms
button on the Setup tab>General menu on the web
interface.
Used to indicate the internal status of the management
module, and to signal warnings and critical alarms.
If the LED is green, the management module has
power, and conditions are normal.
If the LED is green and blinking, communication is
taking place.
If the LED is yellow, a warning has been issued.
If the LED is red, a critical alarm has been issued.
If the LED is blinking green, yellow and red, then a
configuration setting change has been made. To save
the new configuration settings to the internal memory
of the management module, press and hold the C key
for five seconds.
If the LED is off, the management module has no
power.