Configuration Factors; Optimum Environment And Site Preparation; Safety Information - HP MCS-200 User Manual

Modular cooling system 200
Table of Contents

Advertisement

Configuration factors

Optimum environment and site preparation

CAUTION:
service. The water flowing into the MCS-200 unit must meet the guidelines stated in the HP
Modular Cooling System 200/100 Site Preparation Guide. The MCS-200 warranty does not
cover damage caused by contaminated water.
IMPORTANT:
200/100 Site Preparation Guide.
To provide optimum performance with minimum maintenance, your unit must meet environmental
requirements.
The HP Modular Cooling System 200/100 Site Preparation Guide provides information about planning your
unit configuration efficiently and organizing your site location before delivery of your MCS-200 unit.
To route water lines to your MCS-200 unit, use one of the following methods:
Through an opening in the raised floor
Lying on top of the floor
Through the top of the MCS-200 unit
For more information on routing the water lines, see the Hook Up Kit installation instructions in the HP
Modular Cooling System 200/100 Options Installation Guide.

Safety information

The HP Modular Cooling System is tested to the maximum pressure (PS) of 8 bar (116 PSI) without fluid
trapped inside by closed, external valves.
If valves are installed on the external pipe work that could potentially trap fluid inside the MCS-200 unit,
special precautions must be taken. To prevent severe plumbing failure due to extreme pressure, use an
expansion tank with a preinstalled safety valve in the plumbing circuit connected to the unit.
Contaminated water might cause decreased cooling capacity or disruption in
Before you begin the installation process, review the HP Modular Cooling System
Configuration factors 7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents