Manual Operation - Harman P68 Freestanding Pellet Stove Installation & Operating Manual

Freestanding pellet stove
Hide thumbs Also See for P68 Freestanding Pellet Stove:
Table of Contents

Advertisement

Manual constant burn Mode
This setting will produce a large viewing fire without a
distribution blower operating.
17
P68 Pellet Stove

Manual operation

The P68 Pellet Stove is capable of manual operation. This also allows the operator to
manually control operation during an emergency (i.e. igniter failure, or when using certain
generators or other auxiliary power source.)
The unit can be switched between "AUTO" and "MANUAL" at any time during operation.
room temperature Mode: This
setting, see below, will produce a
room temperature of 70° with the
distribution blower at medium
speed.
igniter switch to "Manual"
room temperature Mode
The fire will have to be lit with starting gel and a match,
or started automatically, see "Starting First Fire" under
Automatic Start Up. Turn to "Manual" position after the ignition
cycle begins.
The difference between "AUTO" Room Temperature Mode
and "Manual" Room Temperature Mode is that the fire will
not go out as the room temperature goes above the control
board setting. The unit can only go to low burn and will remain
there until it runs out of fuel or until more heat is needed
and the feed rate increases. Feed rate adjustments and dial
settings are the same as "AUTO" settings. The blower will
shut off completely if the temperature on the ESP is too low.
igniter switch to "Manual"
constant burn Mode
The advantage of this mode is to allow the operator to have
a large viewing fire without blowing extra heat into the room.
During operation, with the temperature dial set at #4 or less,
the distribution fan will not operate. A #4 on the temperature
dial and a #5 on the feed limit is approximately 80% output.
It is not necessary to operate the distribution blower below
this point. This control setting allows a higher burn rate (a
larger viewing fire) without an excess of hot air blowing into
the room.
An example of when to use the Manual Constant burn Mode
is if you want to watch a large fire and the room is already up
to temperature. The Constant burn Mode allows you to have
a larger fire and a lower sound level, without the distribution
blower.
note: during the use of this mode, if you keep increasing
the temperature dial setting to increase the fire size, the
distribution blower will automatically come on when the
esP temperature reaches 350 °F, or 81% output.
3-90-00688R28_03/14

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents