Manual Operation - Harman Advance Freestanding Pellet Stove Installation & Operating Manual

Freestanding pellet stove
Hide thumbs Also See for Advance Freestanding Pellet Stove:
Table of Contents

Advertisement

Room Temperature Mode: This setting will produce a room
temperature of 70 degrees with the distribution blower at medium
speed.
manual Constant burn mode
This setting will produce a large viewing fire without a distribution
blower operating.
6
manual Ignition/Operation
The Advance Pellet Stove is capable of manual operation.
This also allows the operator to manually control operation
during an emergency (i.e. igniter failure.) The unit can be
switched between "AUTO" and "MANUAL" at any time during
operation.
NOTE: It is possible to start a fire in "Auto" and switch
to "manual" at any time. Once an ignition cycle begins,
it will continue, regardless of mode.
room Temperature mode / Igniter switch to "mANuAl"
The fire will have to be lit with starting gel and a match, or
started automatically, see "Automatic Operation". Switch to
"Manual" position after the ignition cycle begins.
The difference between "AUTO" Room Temperature Mode
and "Manual" Room Temperature Mode is that the fire will not
go out as the room temperature goes above the control board
setting. The unit can only go to low burn and will remain there
until it runs out of fuel or until more heat is needed and the
feed rate increases. Feed rate adjustments and dial settings
are the same as "AUTO" settings.
Constant burn mode / Igniter switch to "mANuAl"
The advantage of this mode is to allow the operator to have
a large viewing fire without blowing extra heat into the room.
During operation, with the temperature dial set at #3 or less,
the distribution fan will not operate. A #3 on the temperature
dial and a #5 on the feed adjuster is approximately 80%
output. It is not necessary to operate the distribution blower
below this point. Therefore, there can be a higher feed rate
( a larger viewing fire) without an excess of hot air blowing
into the room.
An example of when to use the Manual Constant Burn Mode
is if you want to watch a large fire and the room is already
up to temperature. The Constant Burn Mode allows you
to have a larger fire and a lower sound level, without the
distribution blower.
NOTE: during the use of this mode, if you keep increasing
the temperature dial setting to increase the fire size, the
distribution blower will automatically come on when the
ESP Temperature reaches 350° F, or 81% output.
1-90-09730R31_05/14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Advance

Table of Contents