Install Outside Air Kit - Heat & Glo RUTHERFORD-50 Owner's Manual

Wood burning fireplace
Hide thumbs Also See for RUTHERFORD-50:
Table of Contents

Advertisement

3 ft min. from
top of uppermost
chimney section
to air inlet.
Figure 7.3
Outside Air Inlet Locations
E. Install Outside Air Kit
Keep duct runs short and straight to minimize
restriction.
The outside air kits must be installed on both sides of the
fireplace.
WARNING! Outside air kits must be installed on both
sides of the fireplace to prevent overheating and fire.
Install as shown in Figures 7.3, 7.4 and 7.5.
The air ducts may be run vertically.
The outside air hoods must be at least 3 ft (.91 m) below
the top of the uppermost chimney section.
CAUTION! Risk of Fire or Asphyxiation! Do not draw
outside combustion air from wall, floor or ceiling cavity, or
enclosed spaces such as an attic or garage.
• DO NOT place outside air hoods close to exhaust
vents or chimneys. Fumes or odor could be drawn
into the room through the fireplace.
• Locate outside air hoods to prevent blockage from
leaves, snow/ice, or other debris. Blockages could
cause the unit to overheat.
NOTICE: The fireplace provides some outside air for
combustion. Other methods may be necessary if more air
is required.
22
Outside air installed
on both sides (right
side not shown)
Heat & Glo • RUTHERFORD-50 • 4059-333 Rev L• 5/11
NO
NO
Garage or
Outlet blocked by
combustible
snow, leaves, etc.
liquids storage
YES
Clear area
outside
house or in
ventilated
Use only duct materials specified by manufacturer (preferably
crawl space
with short run or mainly straight duct, except small dip for cold
air trap which will help prevent flow of cold air).
Figure 7.4
Outside Combustion Air Placement
Flexible Duct
(not supplied)
Outside Air
Hood
2 Wire Ties
Figure 7.5
Outside Air Installation
NO
Attic space
NO
Outlet placed
higher than 3 ft
below the
termination cap
Factory-built
fireplace

Advertisement

Table of Contents
loading

Table of Contents