G. Sidewalls/Surrounds
•
Adjacent combustible sidewalls must be located a
minimum of 24 in. (305 mm) from the fireplace opening.
•
Combustible mantel legs, surrounds and stub walls may
be constructed per Figure 12.10.
Figure 12.10 Combustible Mantel Leg or Wall Projections (Acceptable on both sides of opening)
Heat & Glo • RUTHERFORD-50 • 4059-333 Rev L• 5/11
45