Install Outside Air Kit - Heat & Glo EXCLAIM-36 Owner's Manual

Wood burning fireplace
Hide thumbs Also See for EXCLAIM-36:
Table of Contents

Advertisement

YES
Clear area
house or in
ventilated
crawl space
Figure 7.17 Outside Combustion Air Placement
I. Install Outside Air Kit
CAUTION! Risk of Fire or Asphyxiation! DO NOT draw
outside combustion air from wall, floor or ceiling cavity,
or enclosed spaces such as an attic or garage.
• DO NOT place outside air hood close to exhaust
vents or chimneys. Fumes or odor could be drawn
into the room through the fireplace.
• Locate outside air inlet to prevent blockage from
leaves, snow/ice, or other debris. Blockages could
cause combustion air starvation.
Figure 7.18 Outside Air Installation
NO
Outlet blocked by
snow, leaves, etc.
outside
Use only duct materials specified by manufacturer (preferably
with short run or mainly straight duct, except small dip for cold
air trap which will help prevent flow of cold air).
Flexible Duct
(not supplied)
Outside Air
Shield
2 Wire Ties
Heat & Glo • EXCLAIM-36, EXCLAIM-42 • 4013-251 Rev H• 3/11
NO
Garage or
NO
combustible
liquids storage
Attic space
Factory-built
fireplace
Keep duct runs short and straight to minimize restriction.
A small dip is acceptable for a cold air trap.
The outside air kit must be installed on the left hand side
of the fireplace.
Locate the outside air hood in a clear area, preferably
into prevailing wind during the heating season. Refer to
Figure 5.2.
Install as shown in Figures 7.16, 7.17 and 7.18.
The air duct may be run vertically.
The outside air hood must be at least 3 ft (.91 m) below
the top of the uppermost chimney section.
Inlet Ring
NO
Outlet placed
higher than 3 ft
below the
termination cap
25