[C] Solar priority mode
[C-00] For information concerning the EKSOLHW solar kit, refer
to the installation manual of that kit.
[C-01] Defines the logic of the alarm output on the EKRP1HB
remote alarm input/output PCB.
If [C-01]=0, the alarm output will be powered when an alarm
occurs (default).
If [C-01]=1, the alarm output will not be powered when an alarm
occurs. This field setting allows for distinction between detection
of an alarm and detection of a power failure to the unit.
[C-01]
Alarm
0
Closed output
(default)
1
Open output
[D] Benefit kWh rate power supply
[D-00] Defines which heaters are switched off when the benefit
kWh rate signal of the electricity company is received.
If [D-01]=1 or 2 and the benefit kWh rate signal of the electricity
company is received, following devices will be switched off:
[D-00]
Compressor
0
Forced off
(default)
1
Forced off
2
Forced off
3
Forced off
NOTE
[D-00] settings 1, 2 and 3 are only meaningful if
the benefit kWh rate power supply is of the type
that power supply is not interrupted,
[D-01] Defines whether or not the outdoor unit is connected to a
benefit kWh rate power supply.
If [D-01]=0, the unit is connected to a normal power supply
(default value).
If [D-01]=1 or 2, the unit is connected to a benefit kWh rate
power supply. In this case the wiring requires specific installation
like explained in chapter
power supply" of the installation
When parameter [D-01]=1 at the moment that the benefit kWh
rate signal is sent by the electricity company, that contact will
open and the unit will go in forced off mode
When parameter [D-01]=2 at the moment that the benefit kWh
rate signal is sent by the electricity company, that contact will
close and the unit will go in forced off mode
[E] Unit information readout
[E-00] Readout of the software version (example: 23)
[E-01] Readout of the EEPROM version (example: 23)
[E-02] Readout of the unit model identification (example: 11)
[E-03] Readout of the liquid refrigerant temperature
[E-04] Readout of the inlet water temperature
NOTE
[E-03] and [E-04] readouts are not permanently
refreshed. Temperature readouts are updated
after looping through the field setting first codes
again only.
(1) When the signal is released again, the voltage free contact will close and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to
(2) When the signal is released again, the voltage free contact will open and
the unit will restart operation. It is therefore important to leave the auto
restart function enabled. Refer to
Operation manual
15
No power supply
No alarm
to unit
Open output
Open output
Closed output
Open output
Back up heater
Booster heater
Forced off
Forced off
Forced off
Permitted
Permitted
Forced off
Permitted
Permitted
"Connection to a benefit kWh rate
manual.
(1)
.
(2)
.
"[3] Auto restart" on page
12.
"[3] Auto restart" on page
12.
E(D/B)(H/L)Q011~016AA6V3+W1
Unit for air to water heat pump system and options
4PW51122-1