Power Wiring Details

Each UPS module must be wired to its corresponding module output breaker in the
cabinet with power cables sufficient for carrying the load. Recommended wiring
size is listed in Tables A---3 and A---4 of Appendix A of this manual. Each of the
three phases plus the neutral must be wired. Nonlinear loads can create neutral
currents that are greater than 100%. The neutral bus (terminal strip E12) contains
sufficient cable landing to wire double-size neutrals if needed.
NOTE: Material and labor for external wiring are to be provided by designated
personnel.
Powerware 9315 Parallel Redundant System I & O
22