Refer to the following while installing the parallel cabinet:
·
Dimensions in this manual are in millimeters and inches.
·
Do not tilt the cabinet more than
·
The conduit landing plates are to be removed to add conduit landing holes as
required. Plate material is 16 gauge steel (0.06 in. thick).
·
Terminals E9–E12 and E16---E18 are UL and CSA rated at 90˚C. A hex key tool
is required to attach wires to the terminals.
·
Details about control wiring are provided in Table A---1 of Appendix A and the
Control Wiring Interconnect Details in Chapter 3 of this manual.
Figure 6 shows typical control wiring and power wiring terminations of the UPS
module and parallel cabinet. Refer to the Powerware 9315 Installation manual
provided with the UPS system for location of UPS module cabinet wiring
terminations.
NOTE: Material and labor for external wiring are to be provided by designated
personnel.
Output
Neutral
LEFT DOOR
Connection
(E12)
A/C Output
E9, E10,
E11
TB1
TB3
Terminal Strip
UPS MODULE
Figure 6. Typical Control and Power Wiring Terminations of UPS Module
16
TB2
Communication Panel
(100- - 160kVA UPS Shown)
and Parallel Cabinet
10˚ during installation.
E9
MOB1
ÆB
ÆA ÆC
E16
Ground
PARALLEL CABINET
Powerware 9315 Parallel Redundant System I & O
MOB#1 TB1
E10
E10
E11
E11
E9
MOB2
ÆB
ÆA ÆC
E17 E18
E12
164202013, Rev. D 041599
MOB#2
TB1
Isolated
Ground
(Optional)