Two Elbows
Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
H
2
Figure 7.4
28
WARNING! Risk of Fire!
• TRUE-36(NG/LP),TRUE-42(NG/LP) and TRUE-50(NG/LP) models
require a minimum of 36 inches of vertical venting before attaching
any elbow to the appliance for the venting confi guration in Figure 7.4.
DO NOT attach elbow directly to the appliance.
INSTALLED
HORIZONTALLY
TRUE-36 (NG/LP), TRUE-42 (NG/LP),
TRUE-50 (NG/LP)
V
Minimum
1
3 ft
914 mm
4 ft
1.2 m
5 ft
1.5 m
6 ft
1.8 m
7 ft
2.1 m
8 ft
2.4 m
9 ft
2.7 m
10 ft
3.0 m
V
+ H
+ H
1
1
H
+ H
1
2
Heat & Glo •
TRUE-36, TRUE-42, TRUE-50 • 2282-900 Rev. i •
H
1
H
+ H
1
2
18 in
457 mm
3 ft
914 mm
7 ft
2.1 m
10 ft
3.0 m
14 ft
4.3 m
16 ft
4.9 m
18 ft
5.5 m
20 ft
6.1 m
= 60 ft Maximum
2
= 20 ft Maximum
V
1
4/13