PRODUCT DESIGN
Thermostats:
NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.
Filters:
Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or
CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty.
This furnace has provisions for the installation of return air filters at the side and/or bottom return. The furnace will
accommodate the following filter sizes depending on cabinet size:
Cabinet
Width
Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in
the duct system such as a central return.
COOLING AIRFLOW REQUIREMENT (CFM)
600
800
0453_X*
376*
384
0703_X*
---
564*
0704_X*
---
---
0904_X*
---
---
0905_X*
---
---
1155_X*
---
---
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter Area (in
[Based on a 300 ft/min filter face velocity]
10
SIDE RETURN
Approx.
Nominal
Flow Area
Filter Size
(in.)
(in.)
(in
All
16 x 25 x 1
1000
1200
1400
1600
480
576
---
---
564*
564*
672
---
564*
564*
672
768
752*
752*
752*
768
---
752*
752*
768
---
940*
940*
940*
Upflow Filters

BOTTOM RETURN

Cabinet
Width
2
(in.)
)
400
17-1/2
21
24-1/2
2000
0453_X*
---
0703_X*
---
0704_X*
---
0904_X*
---
0905_X*
800
115_X*
800
*Minimum filter area dictated by heating airflow requirement.
2
)
Permanent Minimum Filter Area (in
[Based on 600 ft/min filter face velocity]
Approx.
Nominal
Flow Area
Filter Size
2
(in.)
(in
)
14 x 25 x 1
350
16 x 25 x 1
400
20 x 25 x 1
500
COOLING AIRFLOW REQUIREMENT (CFM)
600
800
1000
1200
188*
192
240
288
---
282*
282*
282*
---
---
260*
260*
---
---
376*
376*
---
---
---
376*
---
---
---
470*
1400
1600
2000
---
---
---
336
---
---
336
384
---
376*
384
---
376*
384
480
470*
470*
480