MULTIQUIP Power Ultra-Silent DCA-85USJ Operation And Parts Manual page 25

Ultra-silent series generator
Table of Contents

Advertisement

DCA-85USJ — OUTPUT TERMINAL PANEL FAMILIARIZATION
120 VAC GFCI Receptacles
There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R)
recepacles provided on the output terminal panel. These
receptacles can be accessed in any voltage selector switch
position. Each receptacle is protected by a 20 amp circuit
breaker. These breakers are located directly above the GFCI
receptacles. Remember the load output (current) of both
GFCI receptacles is dependent on the load requirements of
the U, V, and W output terminal lugs.
Pressing the reset button resets the GFCI receptacle after
being tripped. Pressing the Test Button (See Figure 9) in
the center of the receptacle will check the GFCI function.
Both receptacles should be tested at least once a month.
Figure 9. G.F.C.I. Receptacle
Twist Lock Dual Voltage 120/240 VAC Receptacles
There are three 120/240V, 50 amp auxilliary twist-lock
(CS-6369) recepacles (Figure 10) provided on the output
terminal panel.These receptacles can only be accessed
when the voltage selector switch is placed in the single-
phase 240/120 position.
Figure 10. 120/240V Twist-Lock
Auxiliary Receptacles
DCA-85USJ — OPERATION AND PARTS MANUAL — REV. #0 (09/17/04) — PAGE 25
Each auxilliary receptacle is protected by a 50 amp circuit
breaker. These breakers are located directly above the GFCI
receptacles. Remember the load output (current) on all three
receptacles is dependent on the load requirements of the
Output Terminal Lugs .
Turn the voltage regulator control knob (Figure 11) on the
control panel to obtain the desired voltage. Turning the knob
clockwise will increase the voltage, turning the knob counter-
clockwise will decrease the voltage.
Figure 11. Voltage Regulator Control Knob
Removing the Plastic Face Plate (Hard Wire Hookup Panel)
The Output Terminal Lugs are protected by a plastic face
plate cover (Figure 12). Un-screw the securing bolts and lift
the plastic terminal cover to gain access to the terminal
enclosure.
After the load wires have been securely attached to the
terminal lugs, reinstall the plastic face plate.
Figure 12. Plastic Face Plate (Output Terminal Lugs)
1

Advertisement

Table of Contents
loading

Table of Contents