Water Piping - Kenmore POWERMISE 12 Owner's Manual

74 gallon (280 liter)
Table of Contents

Advertisement

This water heater should not be connected to any heating
systems or component(s) used with a non-potable water
heating appliance.
All piping components connected to this unit for space
heating applications should be suitable for use with
potable water.
Toxic chemicals, such as those used for boiler treatment should
not be introduced into this system.
Water supply systems may, because of such events as high
line pressure, frequent cut-offs or the effects of water hammer
among others, have installed devices such as pressure
reducing valves, check valves, back flow preventers, etc. to
control these types of problems. When these devices are not
equipped with an internal by-pass, and no other measures are
taken, the devices cause the water system to be closed. As
water is heated, it expands (thermal expansion) and closed
systems do not allow for the expansion of heated water.
The water within the water heater tank expands as it is heated
and increases the pressure of the water system. If the relieving
point of the water heater's temperature-pressure relief valve
is reached, the valve will relieve the excess pressure. The
temperature-pressure relief valve is not intended for the
constant relief of thermal expansion. This is an unacceptable
condition and must be corrected. It is recommended that any
devices installed which could create a closed system have a
by-pass and/or the system have an expansion tank to relieve the
pressure built by thermal expansion in the water system. Refer
to the Thermal Expansion section under Troubleshooting Guide
or contact local plumbing authority or local Sears Service Center
on how to control this situation.
NOTE: To protect against untimely corrosion of hot and cold
water fittings, it is strongly recommended that di-electric
unions or couplings be installed on this water heater when
connected to copper pipe.
Figure 16 shows the typical attachment of the water piping to
the water heater. The 74-gallon model water heater is equipped
with 1" NPT water connections.
TYPICAL INSTALLATION
NOTE: If using copper tubing, solder tubing to an adapter
before attaching the adapter to the water connections. Do
not solder the water lines directly to the water connections
on the tank. It will harm the dip tube and damage the tank.
• Look at the top cover of the water heater. The water outlet is
marked "HOT". Put two or three turns of teflon tape around
the exposed end of the NPT threaded nipple. Connect the hot
water pipe to the hot water outlet on the water heater. Please
note that adapters may be needed to match existing piping.
• Look at the top of the water heater. The cold water inlet
is marked "COLD". Put two or three turns of teflon tape
around the exposed end of the NPT threaded nipple.
Connect the cold water pipe to the cold water inlet of the
water heater. Please note that adapters may be needed
to match existing piping.
NOTE: This water heater is super insulated to minimize
heat loss from the tank. Further reduction in heat loss
can be accomplished by insulating the hot water lines
from the water heater.
13
FIGURE 16.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powermiser 12153.331761

Table of Contents