Figure 2-12 Position Proportional Output Or Three Position Step-Models Dc330X-Ee-Xxx-X2, Dc330X-Aa-Xxx-X2 - Honeywell UDC3300 User Manual

Universal digital controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

Position Proportional Output
Figure 2-12 shows models with Position Proportional Output (Model
DC330X-EE-XXX-X2) or Three Position Step Control (Model DC330X-AA-XXX-X2).
Calibration
Position Proportional Output models must have the output calibrated after
installation. (See Appendix D.)
Three Position Step models only require that the motor time be entered. Full
calibration is not required.
Slidewire 100 to 1000
mechanically linked
to motor
2
Connect shield to ground
at one end only
1
Alarm #2 is not available with Position Proportional output or Three
Position Step control.
2
Do not run slidewire cable in the same conduit as AC power.
3
Electrical noise suppression may be required.
Slidewire input is not required for Three Position Step control but can be
4
used for motor position indication.
Figure 2-12 Position Proportional Output or Three Position Step—
Models DC330X-EE-XXX-X2, DC330X-AA-XXX-X2
5/00
4
3
Cl
Op
Wi
os
en
pe
ed
Op
en
Output
L1
Relay#1
L2/N
22
Output
23
Relay#2
1
24
25
Alarm
26
Relay#1
27
UDC3300 Basic Model: DC330B User Manual
Motor Power
Supply
Neutral
Hot
5 Amp Fast Blo
fuse
Cl
os
ed
1
N.C.
2
N.O.
3
4
N.C.
5
N.O.
6
7
N.C.
Alarm Relay
8
#1 Load
N.O.
9
To terminal
7 or 9
Installation
Load
Supply
Power
5 Amp Fast Blo
fuse
13