Figure 2-12 Position Proportional Output Or Three Position Step-Models - Honeywell DC33XB User Manual

Table of Contents

Advertisement

Position Proportional Output
Figure 2-12 shows models with Position Proportional Output (Model
DC330X-EE-XXX-X2) or Three Position Step Control (Model DC330X-AA-XXX-X2).
Calibration
Position Proportional Output models must have the output calibrated after
installation. (See Appendix D.)
Three Position Step models only require that the motor time be entered. Full
calibration is not required.
Slidewire 100 to 1000 Ω
mechanically linked
to motor
2
Connect shield to ground
at one end only
1
Alarm #2 is not available with Position Proportional output or Three
Position Step control.
2
Do not run slidewire cable in the same conduit as AC power.
3
Electrical noise suppression may be required.
Slidewire input is not required for Three Position Step control but can be
4
used for motor position indication.
Figure 2-12 Position Proportional Output or Three Position Step—
Models DC330X-EE-XXX-X2, DC330X-AA-XXX-X2
12/00
4
3
Cl
Op
Wi
os
en
pe
ed
Op
en
Output
L1
Relay#1
L2/N
22
Output
23
Relay#2
1
24
25
Alarm
26
Relay#1
27
UDC3300 Basic Model: DC33XB User Manual
Motor Power
Supply
Neutral
Hot
5 Amp Fast Blo
fuse
Cl
os
ed
1
N.C.
2
N.O.
3
4
N.C.
5
N.O.
6
7
N.C.
Alarm Relay
8
#1 Load
N.O.
9
To terminal
7 or 9
Installation
Load
Supply
Power
5 Amp Fast Blo
fuse
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Udc3300

Table of Contents