Paragon series
Hide thumbs Also See for Paragon OL1000RMXL2U:

Advertisement

Quick Links

Paragon
OL1000RMXL2U
Series
OL1500RMXL2U
OL2000RMXL2U
OL3000RMXL2U
User Manual

Advertisement

Table of Contents
loading

Summary of Contents for CyberPower Paragon OL1000RMXL2U

  • Page 1 Paragon OL1000RMXL2U Series OL1500RMXL2U OL2000RMXL2U OL3000RMXL2U User Manual...
  • Page 2: About This Manual

    OL1500RMXL2U). - ABP72VRM-2U (72Vdc, 9Ah, for OL2000RMXL2U and OL3000RMXL2U). To learn more about our entire line of CyberPower Systems products and the options available for the Paragon series, visit our web site at www.cyberpowersystems.com or contact your local CyberPower Systems representative.
  • Page 3 OL2000RMXL2U, and OL3000RMXL2U are intended for installation in an environment within 0ºC to 40ºC and free of conductive contaminants. CyberPower Systems pays great attention to the environmental impact of its products. Environmental protection measures for the Paragon series include: • The eco-design approach used in product development.
  • Page 4 Icon Usage Read the following section to familiarize yourself with the icons used in this manual: Icon Description Indicates a hazard to personnel or equipment. These warnings must always be followed. Indicates notes, useful tips, and helpful information. Indicates essential information. LED off.
  • Page 5: Safety Instructions

    Safety Instructions Read before installing SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during installation, operation, and maintenance of the UPS and batteries. CAUTION: Personal Safety ❑ The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC power source.
  • Page 6 CAUTION: Product Safety ❑ The UPS connection instructions and operation described in the manual must be followed in the order indicated. ❑ The UPS must be connected to a nearby wall outlet that is easily accessible. The UPS can be disconnected from the AC power source by removing the power cord.
  • Page 7: Table Of Contents

    Contents Preface ................i Safety Instructions ............. iv Device Overview .............…..1 System configurations ..............1 Rear panel ................… 2 Control panel ................…5 Installation ................…..6 Unpacking ................. …6 Installing the UPS in a rack .............… .7 Setting the UPS in the vertical position ........8 Connecting the RS232 or the USB communication port (optional) ....................
  • Page 8: Device Overview

    Device Overview 1.1 System configurations Rack setup Weight Dimensions Model (pound) (WxDxH)(inch) OL1000RMXL2U 17.24x18.66x3.41 OL1500RMXL2U 17.24x18.66x3.41 45.19 OL2000RMXL2U 17.24x25.69x3.41 70.11 OL3000RMXL2U 17.24x25.69x3.41 72.31 Tower setup Device Overview 1...
  • Page 9: Rear Panel

    1.2 Rear panel Paragon OL1000RMXL2U/OL1500RMXL2U 9 8 6 2 6 7 8 9 Paragon ABP36VRM-2U (optional) Description USB communication port. RS232 communication port. Connector for remote power off (RPO). Connector for automatic detection of an additional battery pack. Expansion slot for optional communication card.
  • Page 10 Paragon OL2000RMXL2U/OL3000RMXL2U 8 7 1 3 2 L5-20R/ L5-30R L5-30P 5-20P (OL3000RMXL2U) 9 (OL2000RMXL2U) Paragon ABP72VRM-2U (optional) Description USB communication port. RS232 communication port. Connector for remote power off (RPO). Connector for automatic detection of an additional battery pack. Expansion slot for optional communication card. Button to test phase/neutral inversion of AC power source.
  • Page 11 The compatibility of optional battery packs: ABP36VRM-2U is for OL1000RMXL2U and OL1500RMXL2U UPS units. ABP72VRM-2U is for OL2000RMXL2U and OL3000RMXL2U UPS units. Refer to the tables in this chapter for all illustration numbering throughout this manual (unless specified otherwise). 4 Device Overview...
  • Page 12: Control Panel

    1.3 Control panel 14 15 17 18 21 22 23 24 Description ON / OFF. BATT: Operation on battery power. INV: Operation in ON-LINE mode (backup power available). BYPASS: Operation on bypass (no backup power available). OUTLET 2: Status of programmable outlet 2. OUTLET 1: Status of programmable outlet 1.
  • Page 13: Installation

    Installation 2.1 Unpacking The following items are included in the box along with the UPS. User’s manual Telescopic rails for mounting in 19” rack with mounting hardware Quick Guide USB communication cable Two tower supports for the vertical position CD with the PowerPanel Business RS232 communication cable software...
  • Page 14: Installing The Ups In A Rack

    2.2 Installing the UPS in a rack Follow the steps below to rack mount the UPS on the rails. The telescopic rails and mounting hardware for rack mounting the UPS have been supplied. 4&5 A. Secure rails together with three screws (1). B.
  • Page 15: Setting The Ups In The Vertical Position

    2.3 Setting the UPS in the vertical position Attach the two tower supports to the UPS as shown below. Pull out the CyberPower Logo plate, rotate it as shown, and replace it in the front of UPS. 8 Installation...
  • Page 16: Connecting The Rs232 Or The Usb Communication Port (Optional)

    (optional) Connect the UPS to a PC using the RS232 or USB communication port as shown below. OL1000RMXL2U/OL1500RMXL2U UPS shown. 1. Connect the RS232 or the USB communication cable to the corresponding port on the computer. 2. Connect the other end of the communication cable to the either...
  • Page 17: Installing The Optional Communication Card

    2.5 Installing the optional communication card OL1000RMXL2U/OL1500RMXL2U UPS shown. It is not necessary to shut down the UPS to install the communication card: 1. Remove the slot cover secured by two screws. 2. Insert the card in the slot. 3. Secure the card with the two screws.
  • Page 18 (D) and any non-priority loads to the two programmable outlets (C). If the UPS is connected to a computer running CyberPower Systems’ communication software, it is possible to program the interruption of power to the two programmable outlets (C) during operation on battery power, thus reserving backup power for the priority loads.
  • Page 19: Operation

    3 Operation 3.1 Start-up The protected equipment connected to the UPS can be powered up, whether AC input power is available or not. 14 15 17 18 21 22 23 The AC input power source must be present when powered by the UPS for the first time.
  • Page 20: Led Indicators

    3.2 LED indicators LEDs provide three different indications: Remaining backup time as a percentage (during normal operation). Percentage of load drawn by the protected equipment, when button is pressed. Operating faults (alarmed by flashing LED and beep): Alarm Condition Site wiring fault Battery fault or end of life warning UPS fault Overload...
  • Page 21: Operation On Battery Power (Following Ac Input Power Failure)

    3.3 Operation on battery power (following AC input power failure) Transfer to battery power The AC power source is out of tolerance, LED is ON, the buzzer sounds three times. The AC power to equipment connected to the UPS is supplied by the battery.
  • Page 22: Personalization (Option)

    End of backup time The buzzer sounds continuously. Press button to turn the buzzer OFF. The equipment is no longer supplied with power. The UPS goes into sleep mode at the end of the battery backup time, until complete shutdown. Make sure that the automatic-restart function has been enabled (Personalization (option) on page 15) for the return of AC input power.
  • Page 23 You can download the PowerPanel Business Edition Agent software from the CyberPower Systems web site at www.cyberpowersystems.com, or contact a CyberPower representative in your area. Once PowerPanel Business Edition Agent has been installed, the UPS parameters listed below can be modified.
  • Page 24 Allow to bypass even if utility power is out of range. Options: Enabled / Disabled Default: Disabled Battery Backup supplies power at the specified voltage. Options: 110 / 120 / 127 Default: 120 Output Frequency Determination - Following utility frequency when it is within the specified tolerance. (default) [When checked, the value can be modified from the drop-down box.] Options: 1~10% Default: 5%...
  • Page 25 Battery Prohibit battery from discharging over 4 hours. Options: Enabled / Disabled Default: Disabled Battery Backup will shut down to save energy if power failed without any load after 5 minutes. Options: Enabled / Disabled Default: Disabled Perform a battery test once during the specified period. Options: every week / every month Default: every week The latest battery replaced date.
  • Page 26: Ups Shutdown

    (RPO) that can cut power from all the devices connected to the UPS using a remote-operated contact. The function is implemented by opening a contact connected to the two terminals of connector the back of the UPS. OL1000RMXL2U/OL1500RMXL2U UPS shown. Operation 19...
  • Page 27 Installation and test of the remote power off function 1. Check that the UPS is shut off and disconnected from the AC power source. 2. Remove the RPO connector by undoing the screws (A). 3. Connect an insulated dry contact (NC, 60V DC, 30V AC max., 20mA max., cable size 0.75mm) to the two terminals of the RPO connector (B).
  • Page 28: Maintenance

    Maintenance 4.1 Troubleshooting If any of LEDs ○ ○ flash, there is an alarm or an abnormal operation. See the table below for problems and solution. If an LED flashes, the bargraph data is no longer displayed. Indication flashes and the buzzer sounds. UPS overload.
  • Page 29 behind the The yellow LED flashes, the red indicator light Indication UPS comes on and the buzzer sounds continuously. The phase and neutral positions of your electrical network are Signification showing reversed positions. Directly grounded neutral type networks: Check the cabling of phase and neutral on your electrical network.
  • Page 30: Replacement Of The Battery Module

    Use tools with insulated handles. Removal of the battery modules : Unclip the small plate with the CyberPower Systems logo on the UPS front panel. : Remove the two screws. Maintenance 23...
  • Page 31 : Remove the left part of the front panel. : Remove the screw and cover plate. : Disconnect the connectors. : Remove the battery modules. Reinstallation of the battery modules To reinstall the battery modules, perform this procedure in reverse order.
  • Page 32: Appendix

    INVERTER BATTERY DC/DC POWER PUSH PULL CHARGER SUPPLY BATTERY 5.2 Technical Specifications OL1000RMXL2U / OL1500RMXL2U / OL2000RMXL2U / OL3000RMXL2U OL1000RMXL2U: 1000/700 OL2000RMXL2U: 2000/1400 Capacity (VA/W) OL3000RMXL2U: 3000/2100 OL1500RMXL2U: 1500/1050 Operation Technology True On-Line & Double Conversion AC Input Number of Phase Single phase (1ψ2W+G)
  • Page 33 Surge Protection Network / Phone / Fax / Modem Surge Protection Battery OL1000RMXL2U: 12V x 7 AH x 3 OL1500RMXL2U: 12V x 9 AH x 3 Voltage x Rating x Quantity OL2000RMXL2U: 12V x 7 AH x 6 OL3000RMXL2U: 12V x 9 AH x 6 Run Time (Full load) >5min @ 25 degree C and full load conditions...
  • Page 34 HTTP/SNMP Card (Optional) Emergency Power Off (EPO) Agency Safety UL1778/cUL CSA22.2 OL1000RMXL2U/OL1500RMXL2U: FCC47 CFR Part 15, Class B EMI / RFI OL2000RMXL2U/OL3000RMXL2U: FCC47 CFR Part 15, Class A IEC 61000-4-2 ESD level 4, IEC 61000-4-3 RS level 3, IEC 61000-4-4 EFT level 4, IEC 61000-4-5 SURGE level 4,...
  • Page 35 Battery Pack Model ABP36VRM-2U ABP72VRM-2U OL2000RMXL2U/ OL1000RMXL2U/ Compatible OL3000RMXL2U OL1500RMXL2U Battery Voltage 12V x 9 AH x 1 2 12V x 7 AH x 6 (2 Strings of 3 (2 Strings of 6 in Serial) Voltage x Rating x Quantity...
  • Page 36: Limited Warranty And Connected Equipment Guarantee

    Limited Warranty. The original end user (referred to as the "Initial Customer") receives an express limited warranty (referred to as the "Limited Warranty") for the OL1000RMXL2U/ OL1500RMXL2U/OL2000RMXL2U/OL3000RMXL2U purchased from CyberPower (referred to as the "Product"). The Limited Warranty is for the Product itself. The terms of the Limited Warranty are explained below.
  • Page 37 CyberPower will inspect and examine the Product within ten (10) days of receipt. If the Product is not as warranted, CyberPower will repair or replace the Product and return it to you at CyberPower's expense, or, if CyberPower is unable to or decides not to repair or...
  • Page 38 (“Primary Coverage”), CyberPower’ will pay only to the extent that the Primary Coverage does not cover the loss. CyberPower's obligation is reduced by any amounts that you are entitled to recover from the Primary Coverage, whether or not you make a claim for recovery under any applicable Primary Coverage.
  • Page 39 CyberPower), or (b) the average price the same or similar items are being sold for on E-bay, or (c) the lowest price the same or similar items can be purchased for in the United States;...
  • Page 40 If CyberPower replaces the connected equipment or pays to the Initial Customer the Agreed Damage Amount, the Initial Customer shall transfer ownership of all item(s) to CyberPower without warranty by the Initial Customer, but free of lien or other interest. CONDITIONS COMMON TO THE LIMITED WARRANTY AND THE...
  • Page 41 DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT OR OTHER HIGH RISK ACTIVITIES. CyberPower does not sell the Products for use in high-risk activities. The Product is not designed or intended for use in hazardous environments requiring fail-safe performance,...
  • Page 42 ANY SUCH USE IS IMPROPER AND IS A MISUSE OF A CYBERPOWER PRODUCTS. The Limited Warranty and the Connected Equipment Guarantee are governed by the laws of the United States and the State of Minnesota, without reference to conflict of law principles.