IMPORTANT SAFETY WARNINGS (SAVE THESE INSTRUCTIONS) This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS. CAUTION! The UPS must be connected to a grounded CAUTION! Do not use an improper size power cord AC power outlet with fuse or circuit breaker protection.
Page 3
INSTALLING YOUR UPS SYSTEM - PACKAGE CONTENTS 1K/1.5KVA or 2.2K/3KVA UPS Serial Interface Cable (RS-232) 12 x screw hole dust covers Left and right rackmount rails 8 x M5X7L black flat head screws 12 x rubber pads Left and right hanging brackets 12 x M5X12L black pan head screws User’s manual, Registration card,...
Page 4
HARDWARE INSTALLATION - RACKMOUNT INSTALLATION FOR 4-POST RACK These versatile UPS systems can be mounted in a rackmount or vertical tower orientation. This versatility is especially important to growing organizations with changing needs that value having the option to position a UPS on a floor or in a rackmount system.
Page 5
HARDWARE INSTALLATION - RACKMOUNT INSTALLATION FOR 4-POST RACK - CONT. Step 4: Adjust rackmount rails to fit your rack How to slide the UPS out from the rack Adjust the rail depth to match your rack depth. Attach The UPS will be secured by a safety locking mechanism each rackmount rail to your rack with two black M5X12L midway of pulling it out of the rack.
Page 6
HARDWARE INSTALLATION - RACKMOUNT INSTALLATION FOR 2-POST RACK Step 2: Rackmount ears installation Due to the weight of this unit, it is Attach the rackmount ears to the center holes on the sides of the UPS using eight black M5X7L screws. strongly recommended to install it at the bottom of the rack.
HARDWARE INSTALLATION - VERTICAL / TOWER INSTALLATION Installation environment should Do not work alone under be in a temperature and humidity hazardous conditions. controlled indoor area free of CAUTION! conductive contaminants. Do not install this UPS where excessive CAUTION! moisture or heat is present (Please In case of the risk of electric shock, see specifications for acceptable do not remove the top cover.
(refer to the When the over temperature occurs, please check technical specifications). the Trouble Shooting section of this manual. If the condition persists, please contact CyberPower for technical support.
Press this button to cancel or return to previous LCD menu. 12. Extended Runtime Battery Module Connector Connection for additional CyberPower External Battery modules. 13. EPO (Emergency Power Off) Connector Enables an emergency UPS Power Off from a remote location.
LCD SETUP FUNCTIONS MULTI-FUNCTION LCD MAIN MENU LCD INFORMATION READOUT 1. Press the ENTER button to activate the MAIN MENU. Press Enter button to activate MAIN MENU 2. Press the s and t buttons to scroll to the Information - Displays the UPS information. Information option.
LCD SETUP FUNCTIONS LCD EVENT LOG 1. Press the ENTER button to activate the MAIN MENU. 2. Press the s and t buttons to scroll to the Event Log option. 3. Press the ENTER button to select the Event Log submenu. 4.
LCD SETUP FUNCTIONS SILENCING AUDIBLE ALARMS 1. Press any of four function buttons on the LCD module. Note: the alarm can not be turned off for a Battery Low condition. This condition will still result in an audible alarm. 2. Change the Audible Alarms option to Disable in the LCD screen and it will no longer give an audible alarm for any malfunction.
LCD MODULE REMOTE CONTROL AND WALL MOUNTING INSTRUCTIONS CAUTION! These operations must be done by qualified personnel. CAUTION! CAUTION! To avoid electric shock, turn off and unplug the unit before installing remote control or mounting on wall. CAUTION! REMOTE CONTROL WALL MOUNTING INSTRUCTIONS Step 1: Remove the Multifunction LCD Control Panel Step 1: Remove the Multifunction LCD Control Panel...
CAUTION! Only use replacement batteries which are store with the battery fully charged. Recharge the battery certified by CyberPower Systems. Use of incorrect battery every three months to ensure battery life. type is an electrical hazard that could lead to explosion, fire, electric shock, or short circuit.
TROUBLESHOOTING Problem Possible Cause Solution Warning Your equipment requires more power than the UPS can provide. If the UPS Shut off non-essential equipment. If this O/P Overload is in Line Mode then it will transfer to solves the overload problem, the UPS will Bypass Mode;...
Page 19
Fault Over Charge Battery is overcharged. 1. Remove battery connector and check charger voltage. 2. Contact CyberPower for repair. Charger Failure Charger has failed. High O/P V Output voltage is too high. 1. Shut down UPS and turn off input breaker.