GLC Circuit Breaker & Electrical Data
Circuit Breaker Size
Qty per Phase
15
20
30
40
50
60
70
80
90
100
110
125
150
175
200
225
250
300
350
400
450
500
600
700
800
900
1000
1200
1400
1600
2000
2500
3000
4000

Wiring Diagrams

Wiring diagrams for these generators are contained on the following pages of this appendix.
MN2408
Min Wire Gauge
1
#16
1
#16
1
#14
1
#12
1
#10
1
#8
1
#8
1
#6
1
#6
1
#6
1
#6
1
#4
1
#2
1
#2
1
#1
1
1/0
1
2/0
1
4/0
1
4/0
2
#1
2
1/0
2
1/0
2
3/0
2
4/0
3
2/0
3
3/0
3
3/0
3
250
4
4/0
4
250
5
250
6
250
7
250
8
300
OSH Plant
1 - #8 EPDM PER PHASE
1 - #8 EPDM PER PHASE
1 - #8 EPDM PER PHASE
1 - #8 EPDM PER PHASE
1 - #8 EPDM PER PHASE
1 - #8 EPDM PER PHASE
1 - #8 EPDM PER PHASE
1 - #8 EPDM PER PHASE
1 - #6 EPDM PER PHASE
1 - #6 EPDM PER PHASE
1 - #6 EPDM PER PHASE
1 - #4 EPDM PER PHASE
1 - #4 EPDM PER PHASE
1 - #1 EPDM PER PHASE
1 - #1 EPDM PER PHASE
1 - #1 EPDM PER PHASE
1 - #1/0 EPDM PER PHASE
1 - #2/0 EPDM PER PHASE
1 - #3/0 EPDM PER PHASE
1 - #4/0 EPDM PER PHASE
2 - #1/0 EPDM PER PHASE
2 - #1/0 EPDM PER PHASE
2 - #2/0 EPDM PER PHASE
2 - #3/0 EPDM PER PHASE
2 - #4/0 EPDM PER PHASE
3 - #2/0 EPDM PER PHASE
3 - #3/0 EPDM PER PHASE
3 - #4/0 EPDM PER PHASE
4 - #4/0 EPDM PER PHASE
4 - #4/0 EPDM PER PHASE
5 - #4/0 EPDM PER PHASE
6 - #4/0 EPDM PER PHASE
7 - #4/0 EPDM PER PHASE
9 - #4/0 EPDM PER PHASE
Ampacity @125C
90
90
90
90
90
90
90
90
125
125
125
170
170
265
265
265
305
355
410
475
610
610
710
820
950
1065
1230
1425
1900
1900
2375
2850
3325
4275