Generator AC Metering The controller is in the display mode at all times except when in the programming
mode. The display screens and menus may be selected by pressing the Enter or Exit keys to
access Operating Status Display, Fault Display, Timer Countdown, Generator AC Metering or
Programming Menus. The LCD display shows the status of the generator output:
Generator Average Output Display
Average Voltage
Average Current
Frequency
Generator KVA Display
KVA
Generator Phase Voltage Display
(Line to Line)
Vab
Vbc
Vca
Generator Phase/Neutral Voltage Display
(Line to Neutral)
Note:
Van
Vbn
Vcn
Generator Phase Current Display
Amps a
Amps b
Amps c
Generator Frequency/Hourmeter Display
FREQ
HOURS
MN2408
Vavg
000
Displays the average generator voltage as follows:
3-phase system: AVERAGE LINE TO LINE VOLTAGE--Phases
1-phase system: LINE TO LINE VOLTAGE--Phases A to B
Displays the average generator current as follows:
3-phase system: AVERAGE LINE CURRENT--Phases A,B,C
1-phase system: AVERAGE LINE CURRENT--Phases A,B
Displays generator frequency in hertz (HZ). The frequency is displayed with a resolution of 1/10 of a hertz.
Displays the generator's total power output in kilo-voltamperes (KVA).
Vab
600
Displays the generator's output voltage:
3-phase system: LINE TO LINE VOLTAGE--Phases A to B
1-phase system: LINE TO LINE VOLTAGE--Phases A to B
Displays the generator's output voltage:
3-phase system: LINE TO LINE VOLTAGE--Phases B to C
1-phase system: LINE TO NEUTRAL VOLTAGE--Phases A-N
Displays the generator's output voltage:
3-phase system: LINE TO LINE VOLTAGE--Phases C to A
1-phase system: LINE TO NEUTRAL VOLTAGE--Phases B-N
Van
347
The generator's neutral must be connected to controller terminal TB1-VN and the "neutral connected" prompt in the main
program menu must be selected as "Yes".
Displays generator voltage Phase A to Neutral.
Displays generator voltage Phase B to Neutral.
Displays generator voltage Phase C to Neutral.
Amps
Displays generator load current as follows:
3-phase system: PHASE A CURRENT
1-phase system: PHASE A CURRENT
Displays generator load current as follows:
3-phase system: PHASE B CURRENT
1-phase system: PHASE B CURRENT
Displays generator load current as follows:
3-phase system: PHASE C CURRENT
1-phase system: not applicable
FREQ
HOURS
Displays generator frequency in hertz (HZ). The frequency is displayed with a resolution of 1/10 of a hertz.
Displays unit operating hours.
Aavg
Freq
000
000
KVA
632.23
Vbc
Vca
600
600
Vbn
Vcn
347
347
a
b
c
408
451
415
60.1 Hz
56788 Hrs
Operation 4‐23