Alarms

Following alarms are available:
Sensor fail (FLS) see Table 4‐10
Sensor fail is detected when measured value is 6% out of selected sensor characteristic.
Sensor fail is indicated by ##### symbol instead measured value.
Warning (WRN) see Table 4‐10
When warning comes up, only alarm outputs and common warning output are closed.
Shut down (SD) see Table 4‐10
When the shut-down alarm comes up, InteliLite opens outputs GCB CLOSE/OPEN, FUEL
SOLENOID, STARTER and PRESTART to stop the engine immediately. Alarm outputs and
common shutdown output are closed. Active or not reset protection disables start.
Events specification
Wrn Oil press
Sd Oil press
Wrn Water temp
Sd Water temp
Wrn Wtemp Low
Wrn Fuel Level
Sd Fuel Level
Battery voltage <, >
Battery flat
Start fail
Vgen <, >
Vgen unbl
Fgen <, >
Igen unbl
Overload
RPM over
RPM under
PickupFault
Stop fail
WrnServiceTime
Emergency Stop
ECU Common Warning
ECU Shutdown
4‐4 Operation
Table 4‐10 Possible Warnings
Protection type
WRN
SD
WRN
SD
WRN
WRN
SD
WRN
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
WRN
SD
WRN
SD
MN2408