Netaxs-123/Netaxs-123 Access Controller Panel Connection Detail; Figure 22: Netaxs-123/Netaxs-123 Access Controller Panel Connection Detail - Honeywell NetAXS-123 Installation Manual

Access control unit
Hide thumbs Also See for NetAXS-123:
Table of Contents

Advertisement

Installing the NetAXS-123 Panels
System Configuration

4.10 NetAXS-123/NetAXS-123 Access Controller Panel Connection Detail

Figure 22: NetAXS-123/NetAXS-123 Access Controller Panel Connection Detail

485 +
485 -
485 Com
58
www.honeywell.com
DIP Switch Settings
S1-S5: Panel Address
S6: ON: GATEWAY
S7: OFF
S8-S9 ON: 485 Termination ON
NetAXS-123
C-TB9
DC Out
A
B
COM
+24VDC in
DIP Switch Settings
S1-S5: Panel Address
S6: ON: GATEWAY
S7: OFF
S8-S9 ON: 485 Termination ON
485 Common
485 -
485 +
NetAXS-123
C-TB9
DC Out
485 +
A
485 -
B
485 Com
COM
+24VDC in
DIP Switch Settings
S1-S5: Panel Address
S6: OFF
S7: OFF
S8-S9 OFF: 485 Termination OFF
Shield
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)
Ground Shield
X
DO NOT CONNECT or
GROUND SHIELD
NetAXS-123
C-TB9
DC Out
485 +
A
485 -
B
485 Com
COM
+24VDC in
Ground only one
side of cable shield