Neutral-To-Ground Bonding For Isolated Output - Eaton Powerware 9170+ UPS 3–18 kVA User Manual

Powerware series 3–18 kva
Table of Contents

Advertisement

ISOLATED OUTPUT WIRING DIAGRAMS

Neutral-to-Ground Bonding for Isolated Output

54
+
Eaton 9170
UPS (3–18 kVA) User's Guide
100/200, 110/220, 115/230, or 120/240V Out
Menu 4 2 4 set to 200, 220, 230, or 240, as required.
X1
X
L1
Figure 35. Isolated Outputs – Single-Phase Voltages
Menu 4 2 4 set to 208 or 220, as required.
X1
Figure 36. Isolated Outputs – Derived Three-Phase Voltages
As required under safety regulations issued by various regulatory
agencies, the UPS cabinet must have a ground-bond connection for the
neutral terminal of an isolated-output system. In such a system, the
customer must make the neutral-to-ground (also referred to as N-G or
neutral-to-earth) connection after selecting the desired output
configuration.
In isolated-output systems, connect the neutral-to-ground (neutral-to-earth)
wire to the proper terminal before making any other connections to the UPS. A
green and yellow neutral-to-ground bonding wire is supplied, with one
end connected to the ground (earth) UPS terminal as shown in
Figure 37. The other end of the wire (as shown by * in Figure 37) must
be attached to the proper output neutral terminal, as specified in
Figure 35 and Figure 36.
S
164201393 Rev E www.eaton.com/powerquality
50 or 60 Hz
with Isolated Output Option
X3
X0
X
N-G Bond
100, 110,
100, 110,
115, or 120
115, or 120
200, 220, 230, or 240
N
50 or 60 Hz
120/208 or 127/220V Out
with Isolated Output Option
X3
X0
X
X
N-G Bond
88 or 93
120 or 127
208 or 220
L1
N
X2
X
L2
X2
X
L2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware 9170+9170 +

Table of Contents