Ups With Bypass Electrical Installation - Eaton Powerware 9170+ UPS 3–18 kVA User Manual

Powerware series 3–18 kva
Table of Contents

Advertisement

Chapter 3
Eaton 9170

UPS with Bypass Electrical Installation

NOTE If you have a plug-receptacle unit, continue to "Battery Cabinet Installation" on
page 61 for installing optional battery cabinets or to "UPS Startup" on page 67.
Only qualified service personnel (such as a licensed electrician) should perform the electrical
installation. Risk of electrical shock.
The Eaton 9170+ UPS input power may be hardwired through conduit to
either a main power source circuit breaker or to an optional external
bypass switch. For hardwired installations, it is recommended that you
install an Eaton bypass switch to enable power transfer during
maintenance or UPS downtime. If a bypass switch is used, both UPS
input and UPS output must be hardwired — through separate
conduits — to the bypass switch, as shown in Figure 12.
+
UPS (3–18 kVA) User's Guide
W A R N I N G
S
164201393 Rev E www.eaton.com/powerquality
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware 9170+9170 +

Table of Contents