Lenovo ThinkServer RD120 Hardware Maintenance Manual page 195

Hardware maintenance manual for rd120
Hide thumbs Also See for ThinkServer RD120:
Table of Contents

Advertisement

v Follow the suggested actions in the order in which they are listed in the Action column until the problem
is solved.
v See Chapter 3, "Parts listing, ThinkServer RD120 Machine Types 6444, 6445, 6446, and 6447," on page 25
to determine which components are customer replaceable units (CRU) and which components are field
replaceable units (FRU).
v If an action step is preceded by "(Trained service technician only)," that step must be performed only by a
trained service technician.
Error code
Description
166-407-001
System Management: Failed.
BMC indicates failure in I
166-nnn-001
System Management: Failed.
Note: nnn indicates the failure type.
v 300 to 320: Self-test failure
v 400 to 420 (excluding 412, 414, and 415):
2
I
C bus test failure
Action
1. Disconnect all power cords and external cables
2
C bus test.
from the server, wait 30 seconds, reconnect the
power cords and cables, and retry the test.
Attention:
trained service personnel other than Lenovo
service technicians are authorized to connect or
disconnect power to the dc power supply. See the
documentation that comes with each dc power
supply.
2. Update the BMC firmware to the latest level.
3. Reseat the operator information panel cable.
4. Replace the following components one at a time,
in the order shown, restarting the server each
time:
a. Operator information panel assembly
b. (Trained service technician only) System
1. Disconnect all power cords and external cables
from the server, wait 30 seconds, reconnect the
power cords and cables, and retry the test.
Attention:
trained service personnel other than Lenovo
service technicians are authorized to connect or
disconnect power to the dc power supply. See the
documentation that comes with each dc power
supply.
2. Update the BMC firmware to the latest level.
3. (Trained service technician only) Replace the
system board.
In a dc power environment, only
board
In a dc power environment, only
Chapter 5. Diagnostics
177