Comparison of the System and Standard Functions of PROFINET IO and PROFIBUS DP
For CPUs with an integrated PROFINET interface, the table below provides you with an
overview of:
• System and standard functions for SIMATIC that you may need to replace when
• New system and standard functions
Table 3-6
Blocks
SFC13 (read diagnostic data of
a DP slave)
SFC58/59 (write/read data
record in I/O)
SFB52/53 (read/write data
record)
SFB54 (evaluate alarm)
SFC102 (read predefined
parameters)
new:
SFB81 (read predefined
parameters)
SFC5 (query start address of a
module)
new:
SFC70 (query start address of a
module)
SFC49 (query the slot belonging
to a logical address)
new:
SFC71 (query the slot belonging
to a logical address)
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
converting from PROFIBUS DP to PROFINET IO.
New System Standard Functions of PROFINET IO and PROFIBUS DP and Those That
Must Be Replaced
PROFINET IO
No
Substitute:
event-related: SFB 54
•
state-related: SFB 52
•
No (replacement: SFB53/52)
Yes
Yes
No (replacement: SFB81)
Yes
No (replacement: SFC70)
Yes
No (replacement: SFC71)
Yes
Communication
3.2 Communication services
PROFIBUS DP
Yes
yes (but should already have
been replaced by SFB53/52 in
DPV1)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes