Technical data of CPU 31x
7.3 CPU 314
Technical data
MPI
Services
•
•
•
•
•
•
Programming
Programming language
Available instructions
Nesting levels
System functions (SFCs)
System function blocks (SFBs)
User program security
Dimensions
Mounting dimensions W x H x D (mm)
Weight
Voltages and currents
Power supply (rated value)
•
Current consumption (no-load operation)
Inrush current
Power consumption (nominal value)
I
t
2
External fusing of power supply lines
(recommended)
Power loss
7-12
PG/OP communication
Routing
Global data communication
S7 basic communication
S7 communication
As server
–
As client
–
Transmission rates
Permitted range
Yes
No
Yes
Yes
Yes
Yes
No (but via CP and loadable FBs)
187.5 kbps
LAD/FBD/STL
See the Instruction List
8
See the Instruction List
See the Instruction List
Yes
40 x 125 x 130
280 g
24 VDC
20.4 V to 28.8 V
Typically 60 mA
Typically 2.5 A
0,6 A
0.5 A
s
2
min. 2 A
Typically 2.5 W
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05