Technical data of CPU 31xC
6.6 Technical data of the integrated I/O
Technical data
Time constant of the input filter
Basic processing time
Interference suppression, error limits
Interference voltage suppression for f = nx (f1 ± 1 %), (f1 = interference
frequency), n = 1, 2
Common­mode interference (U
Feedback interference (peak value of the interference < rated value of
the input range)
Crosstalk between the inputs
Operational error limits (across the temperature range, in relation to input
range)
Voltage/current
Resistance
Basic error limit (operational limit at 25 °C, in relation to input range)
Voltage/current
Resistance
Temperature error (in relation to input range)
Linearity error (referred to input range)
Repeat accuracy (in transient state at 25 °C, in relation to input range)
Status, interrupts, diagnostics
Interrupts
Diagnostics functions
Encoder selection data
Input ranges (rated value)/input resistance
Voltage
Current
Resistance
Resistance thermometer
Permitted continuous input voltage (destruction limit)
For voltage inputs
For current inputs
Permitted continuous input current (destruction limit)
For voltage inputs
For current inputs
6-52
< 1.0 V)
CM
0,38 ms
1 ms
> 40 dB
> 30 dB
> 60 dB
< 1 %
< 5 %
< 0,7 %
< 3 %
± 0,006 %/K
± 0,06 %
± 0,06 %
no interrupts when operated as standard
I/O
no diagnostics when operated as
standard I/O
For using technological functions, please
Technological Functions
refer to the
Manual.
± 10 V/100 kΩ
0 V to 10 V/100 kΩ
± 20 mA/50 Ω
0 mA to 20 mA/50 Ω
4 mA to 20 mA/50 Ω
0 Ω to 600 Ω/10 MΩ
Pt 100/10 MΩ
Max. 30 V
Max. 2.5 V
Max. 0,5 mA;
Max. 50 mA;
CPU 31xC and CPU 31x, Technical data